Product Number
Structural Features
Main Parameters And Technical Performance
Shape And Installation Dimensions(mm)
● The starter is of protective type, plastic shell type (JLE1-09~32) and metal shell type (JLE1- 40~95), and the protection level can reach IP65; ● The operating mechanism is a manual start and stop button, and the starter is an irreversible starter with a thermal (overload) relay; ● The JLE1 AC contactor with 35mm standard rails selected in the starter can be directly buckled on the base of the starter. The thermal (overload) relay three-phase lead hard wire can be directly inserted into the three-phase main contact of the contactor, which is convenient for assembly and wiring.● The main technical performance indicators and component equipment of the starter (see Table 1); ● The starter rated control circuit voltage Us is: AC 50/60Hz, 24V, 42V, 110V, 220/230V, 240V, 380/400V, 415V, 440V, 480V, 6OOV; ● Range of action: ○ Pull-in voltage: 50 or 60H 80%Us-110% Us; 50/60Hz 85%Us~110%Us; ○ Release voltage: 20%Us-75%Us ● The operating range of the starter with thermal (overload) relay has the operating characteristics of thermal relay; 5. The operating frequency with thermal relay is 30 times/hour;Technical Parameters
Type | Maximum power AC3 duty(KW) | Rated current(A) | Type of enclosure | Suitable Thermal Relay(A) | |||||
220V 230V | 380V 400V | 415V | 440V | 500V | 660V 690V | ||||
JLE1-D09 | 2.2 | 4 | 4 | 4 | 5.5 | 5.5 | 9 | IP42 IP65 | JLR2-D1312 JLR2-D1314 |
JLE1-D12 | 3 | 5.5 | 5.5 | 5.5 | 7.5 | 7.5 | 12 | IP42 IP55 | JLR2-D1316 |
JLE1-D18 | 4 | 7.5 | 9 | 9 | 10 | 10 | 18 | IP42 IP55 | JLR2-D1321 |
JLE1-D25 | 5.5 | 11 | 11 | 11 | 15 | 15 | 25 | IP42 IP55 | JLR2-D1322 JLR2-D2353 |
JLE1-D32 | 7.5 | 15 | 15 | 15 | 18.5 | 18.5 | 32 | IP55 | JLR2-D2355 |
JLE1-D40 | 11 | 18.5 | 22 | 22 | 22 | 30 | 40 | IP55 | JLR2-D3353 JLR2-D3355 |
JLE1-D50 | 15 | 22 | 25 | 30 | 30 | 33 | 50 | IP55 | JLR2-D3357 JLR2-D3359 |
JLE1-D65 | 18.5 | 30 | 37 | 37 | 37 | 37 | 65 | IP55 | JLR2-D3361 |
JLE1-D80 | 22 | 37 | 45 | 45 | 55 | 45 | 80 | IP55 | JLR2-D3363 JLR2-D3365 |
JLE1-D95 | 25 | 45 | 45 | 45 | 55 | 45 | 95 | IP55 | JLR2-D3365 |
Enclosure | LE1-D09 and D12 | Double insulated, protexted to IP 429(3) or to IP 659(4) | |||||||
LE1-D18 and D25 | Double insulated, protexted to IP 427(3) or to IP 557(4) | ||||||||
LE1-D32…D95 | Metal, IP 55 to IP 559 | ||||||||
Control(2 pushbuttons mounted on enclosure cover) | LE1-D09…D95 | 1 green Start button "I" 1red Stop/Reset button"O" | |||||||
Connections | LE1-D32…D95 | Pre-wired power and control circuit connections | |||||||
Standard control circuit voltages | |||||||||
Volts | 24 | 42 | 48 | 110 | 220/230 | 230 | 240 | 380/400 | 440 |
50/60HZ | B7 | D7 | E7 | F7 | M7 | P7 | U7 | Q7 | R |